3 Assembly and installation
BU 0530 GB-3712 33
3.4.3 Details of the "Safe pulse block" control connections
NOTE
As delivered, for commissioning without safety switching device, terminals 87-88 and 86-89 are
bridged. In order to be able to use the safety function, the bridges must be removed.
Terminal block X8 Safe pulse lock (not with 115V devices)
Relevance
SK 500E
SK 505E
SK 510E
SK 511E
SK 515E
SK 520E
SK 530E
SK 535E
SK 540E
SK 545E
Terminal X8:
86
87
88
89
VO_S 15V
VO_S 0V
VI_S 0V
VI_S 24V
Designation
Terminal
Function
[factory setting]
Data
Description / wiring suggestion
Parameter
up to SK
535E
SK 540E
and above
86
Supply voltage
15V 20%
When setting-up without using a
safety function, wire directly to V_IS
24V.
P420 et
seqq.
P420 [-…]
87
Reference potential
88
Reference potential
24V 25%, ≤140mA
See technical data in
BU0530!
Fail-safe input
89
Input,
safe pulse lock
Relevance
SK 500E
SK 505E
SK 510E
SK 511E
SK 515E
SK 520E
SK 530E
SK 535E
SK 540E
SK 545E
Terminal X8:
86
87
88
89
VO_S 24V
VO_S 0V
V_S 0V
VI_S 24V
Designation
Terminal
Function
[factory setting]
Data
Description / wiring suggestion
Parameter
up to SK
535E
SK 540E
and above
86
Supply voltage
18-30V, each to VI
24V
When setting-up without using a
safety function, wire directly to V_IS
24V.
P420 et
seqq.
P420 […]
87
Reference potential
88
Reference potential
24V 25%, ≤140mA
See technical data in
BU0530!
Fail-safe input
89
Input,
safe pulse lock